TU IOE · EE 702

Utilization of Electrical Energy

Chapters
6
Questions
222

Past questions by syllabus

6.

Demand Side Management

6.4

Causes and Disadvantages of Low Power Factor and Different Techniques to Improve Power Factor

10 questions
  1. 2081 Bhadra2076 Chaitra2075 AshwinChapter 6: Demand Side ManagementCauses and Disadvantages of Low Power Factor and Different Techniques to Improve Power Factor

    A 35 kW induction motor has pf 0.9 and efficiency 0.9 at full load, pf 0.6 and efficiency 0.7 at half load. At no load, the current is 25% of full load current and pf 0.1. Capacitors are supplied to make the line pf 0.8 at half load. With these capacitors in circuit, find the line pf at (i) full load (ii) no load.

    ASK ON:ChatGPTClaude8 marks Asked 3×
6.5

Types of Tariff: Simple Tariff, Flat-Rate Tariff, Block-Rate Tariff, Two Part Tariff, Maximum Demand Tariff

11 questions
  1. 2080 Baishakh2076 Ashwin2072 KartikChapter 6: Demand Side ManagementTypes of Tariff: Simple Tariff, Flat-Rate Tariff, Block-Rate Tariff, Two Part Tariff, Maximum Demand Tariff

    A 340 kW, 50Hz, 3 phase star connected induction motor has full load efficiency of 85% and p.f of 0.8 lagging. It is desired to improve the power factor to 0.96 lagging by using bank of three capacitors. Calculate: (i) The kVAR rating of the capacitor bank. (ii) The capacitance of each limbs of the condenser bank connected in delta. (iii) The capacitance of each capacitor, if each one of the limb of the delta-connected condenser bank is formed by using 6 similar 3300v capacitors.

    ASK ON:ChatGPTClaude8 marks Asked 3×
6.6

Tariff System in Nepal

1 question